Cisco 7204 Installation and Configuration Guide
OL-5101-01
Chapter 5      Troubleshooting the Installation
  Troubleshooting the Cooling Subsystem
If the I/O controller enabled LED does not go on as expected, make sure the power to the router is turned 
off, reseat the network processing engine in its slot, and restart the router.
If the enabled LED remains off, the system detected a processor hardware failure. (This LED should be 
on in normal operation.) Contact a service representative for instructions.
Troubleshooting the Port Adapters and Service Adapters
Check the following to help isolate a problem with the port or service adapters:
Are all adapter enabled LEDs on?
If yes, the system is operational. 
Are any adapter enabled LEDs off?
If the enabled LED on an individual adapter is off, suspect that the adapter has pulled away from 
the midplane. Reseat the adapter in its slot (you do not have to turn off the system power when 
removing or replacing port or service adapters). After the system reinitializes the interfaces (if 
present—service adapters do not have interfaces), the enabled LED on the adapter should go on.
If the enabled LED remains off, the system detected a processor hardware failure. (This LED 
should be on in normal operation.) Contact a service representative for instructions.
Troubleshooting the Cooling Subsystem
Check the following to help isolate a problem with the cooling system:
When you start up the system, do the fans start operating?
To determine if the fans are operating, listen for them. In noisy environments, place your hand on 
the left side of the chassis (when viewing the chassis from the front) to feel for air being forced out 
the vents.
If yes, the power to the fan tray is good.
If no, there is a problem with the fan tray or power. Refer to the section “Troubleshooting the 
Power Subsystem” in this chapter.
The following message, if displayed, indicates that the system has detected an overtemperature 
condition or out-of-tolerance power inside the chassis. 
Queued messages:
%ENVM-1-SHUTDOWN: Environmental Monitor initiated shutdown
If an environmental shutdown results from an out-of-tolerance power condition, the power OK LED 
will go off, and the system shuts down. (Refer to the 
 .) Although an overtemperature condition is unlikely at initial startup, ensure 
that heated exhaust air from other equipment is not entering the router’s inlet vent, and that there is 
sufficient clearance around the sides of the chassis to allow cooling air to flow. Refer to the 
 for preventive site configurations.
The above message could also indicate a faulty component or temperature sensor. Before the system 
shuts down, use the show environment or show environment table command to display the internal 
chassis environment. (Refer to the 
 in 
 for descriptions of the show environment and show environment table 
commands.)