Chapter 3 Creating and Editing Screens 
Revision May, 2010 
 
 
3-173 
Property Description of X-Y Chart Elements 
Sample Number 
Max. Sample 
Number 
 
Please note that when the sample number is a 
constant, the Max. Sample Number option is 
disabled.  
When Sample Number is a variable value
When the sample number is set to the address 
(register), the sample number is a variable value. The 
user can change the value of the address to modify 
the sample number at the same time. When the 
sample number is a variable value, the Max. Sample 
Number option must be set. If the read value is more 
than the set Max. Sample Number, the system will 
take the set Max. Sample Number as the actual 
maximum sample number. 
Data Format 
Word 
1. 
BCD 
2. 
Signed BCD 
3. 
Signed Decimal 
4. 
Unsigned Decimal 
5. 
Hex 
Setting 
Horiz. Read 
Address 
The address can be internal memory or the controller 
address. (Please refer to Table 3.2.2 Property 
Description of General Buttons.) 
The X-Y chart will continuously read numbers of 
addresses from the horizontal read address set by 
the user, convert the read data into the points of 
X-axis and display on HMI screen. The numbers of 
the addresses is determined by the setting of 
“Sample Number”.