Chapter 4
Human Machine Interface
© National Instruments Corporation
4-25
General Principles of G HMI Programming
You can choose how to monitor and control tag values as well as operator 
interface controls and indicators in your HMI. Normally, you use one or 
more While Loops in a VI diagram with a single wait operation inside of 
each loop. Each While Loop executes once after its wait operation 
completes. The wait operation might be one of the Time and Dialog 
functions such as the Wait Until Next ms Multiple function. This is a polled 
technique in which your diagram controls loop execution. 
Alternatively, the wait operation might be implemented using one of the 
Tags VIs or Alarms and Events VIs with timeout wired to a non-zero value. 
These are the types of diagrams created by the HMI G Wizard. This is an 
event-driven technique, in which a tag or alarm event controls loop 
execution. Either technique is appropriate, depending on your HMI needs. 
You can wait on multiple events for which timing is not related to each 
other in parallel on the same diagram, as long as you wait for each event in 
a separate While Loop. This section covers the following topics:
Event-driven programming
Polled programming
Multiple loop applications
Real-time trends
Programmatic HMI indicator configuration
How Do You Implement Event-Driven Programming in G?
Event-driven programming means your block diagram waits for one or 
more events to happen and, as each event occurs, the part of your program 
waiting on that event is executed. In G, you can develop applications that 
wait on different events and do operations in parallel by using multiple 
While Loops in your diagram.
Figure 4-3 shows an example using event-driven programming to monitor 
tag value and tag alarm state. One loop monitors the value of the 
Mixer
 tag 
and another loop monitors alarm information for the 
Mixer
 tag. These two 
loops run independently of each other. When the 
Mixer
 tag value changes, 
or when 
1.00
 second has elapsed, the Read Tag VI returns and updates the 
Mixer in Alarm
Mixer
value timestamp
, and 
bad value
 
indicators. When the 
alarm state
 of the 
Mixer
 tag changes, or 
5.00
 
seconds have elapsed, the Read Tag Alarm VI returns and updates the