Priority stops
 
50
CiA402 profile
Fixed assignments are configured by the following values:
Cp11
 is assigned by default to the reverse direction command 
[Reverse assign.]
 
(rrS)
.
At the terminals:
(1)
 If the assignment is fixed, the value necessary for starting, even if another channel is active.
In run on edge command, configured by 
[3 wire]
 
(3C)
, the stop command (run enable) is assigned by construction to 
LI1
. This command 
is active even if the terminals are not the active channel.
Via the network:
(1)
 If the assignment is fixed, the value necessary for starting, even if another channel is active.
In the CiA402 profile, the freewheel stop command 
[Freewheel stop ass.]
 
(nSt)
 cannot be assigned to the control word. Freewheel stop is 
obtained via the "5-Disable operation" or "Halt" command with the Type of Stop 
[Type of stop]
 
(Stt)
 parameter configured to 
[Freewheel]
(nSt)
.
In the CiA402 profile, separate or not separate mode:
External stop and fault commands, configured as fixed assignments (
LIpp
C1pp
C2pp
C3pp
C4pp
), on terminal inputs or control word 
bits, have priority even if the channel is not active.
Commands, configured as switched assignments (
Cd11
 ... 
Cd15
), are active if and only if the channel is active.
Channel
Run on state command
[2 wire]
 
(2C)
Run on edge command
[3 wire] 
(3C)
Drive terminals
LI2
 ... 
LI6
LI3
 ... 
LI6
Logic I/O card
LI7
 ... 
LI10
Extended I/O card
LI11
 ... 
LI14
Integrated Modbus
C111
 ... 
C115
CANopen
C211
 ... 
C215
Communication card
C311
 ... 
C315
"Controller Inside" card
C411
 ... 
C415
Command
Configuration
= 0
= 1
Value for 
starting
(1)
State reached from
5-Operation enabled
Freewheel stop
[Freewheel stop ass.]
 
(nSt)
Stop
No stop
1
2-Switch on disabled
Fast stop
[Fast stop assign.]
 
(FSt)
Stop
No stop
1
4-Switched on
DC injection braking
[DC injection assign.]
 
(dCI)
No braking
Braking
0
5-Operation enabled
External fault
[External fault ass.]
 
(EtF)
No fault
Fault
0
8-Fault
Command
Configuration
= 0
= 1
Value for 
starting
(1)
State reached from
5-Operation enabled
Fast stop
[Fast stop assign.]
 
(FSt)
No stop
Stop
0
4-Switched on
DC injection braking
[DC injection assign.]
 
(dCI)
No braking
Braking
0
5-Operation enabled
External fault
[External fault ass.]
 
(EtF)
No fault
Fault
0
8-Fault