Schneider Electric 61 Manual De Usuario

Descargar
Página de 131
73
Loading drive parameters
 
Inconsistency examples
The 2 adjustment parameters
 [Low speed]
 (3105-
LSP
) and 
[High speed]
 (3104-HSP) comply with the consistency rule: 
 
[Low speed]
 (3105-
LSP
y
 [High speed]
 (3104-
HSP
y 10000.
Example 1
Initial configuration 
Configuration to be loaded:
[High speed]
 (3104-
HSP
) = 30 Hz 
V
 
[High speed]
 (3104-
HSP
) = 60 Hz
[Low speed]
 (3105-
LSP
) = 20 Hz    
[Low speed]
 (3105-
LSP
) = 40 Hz
• "Request n:  Request writing of 
[Low speed]
 (3105-
LSP
) to 40 Hz
• "Consistency check:  The consistency rule 
[Low speed]
 (3105-
LSP
y
 [High speed]
 (3104-
HSP
) is not complied with: 
- The 
[Low speed]
 (3105-
LSP
) parameter actually written into the drive is 30 Hz.
• "Request n+1:  Request writing of
 [High speed]
 (3104-
HSP
) = 60 Hz
• "Consistency check:  The consistency rules are complied with:
- The 
[High speed]
 (3104-
HSP
) parameter is correctly written to 60 Hz in the drive. 
The configuration loaded is different from the configuration to be loaded:
[Low speed]
 (3105-
LSP
) = 30 Hz instead of
 [Low speed]
 (3105-
LSP
) = 40 Hz
The drive can operate between 30 Hz and 40 Hz, which is not desired.
Example 2
Initial configuration 
Configuration to be loaded:
[High speed]
 (3104-
HSP
) = 60 Hz 
V
 
[High speed]
 (3104-
HSP
) = 30 Hz
[Low speed]
 (3105-
LSP
) = 40 Hz    
[Low speed]
 (3105-
LSP
) = 0 Hz
• "Request n:  Request writing of
 [High speed]
 (3104-
HSP
) to 30 Hz 
• "Consistency check: The consistency rule 
[Low speed]
 (3105-
LSP
[High speed]
 (3104-
HSP
) is not complied with:
- The 
[High speed]
 (3104-
HSP
) parameter actually written into the drive is 40 Hz. 
• "Request n+1: Request writing of 
[Low speed]
 (3105-
LSP
) = 0 Hz
• "Consistency check: The consistency rules are complied with:
- The 
[Low speed]
 (3104-
HSP
) parameter is correctly written to 0 Hz in the drive.
The configuration loaded is different from the configuration to be loaded:
[High speed]
 (3104-
HSP
) = 40 Hz instead of 
[High speed]
 (3104-
HSP
) = 30 Hz