Setpoint parameters
 
78
PISP
Parameter name:
PID regulator reference
Logic address:
8503 = 16#2137
Type:
INT
CANopen index:
2037/4
Read/write:
R/W
INTERBUS index:
5FB6/1D
Unit:
1
DeviceNet path:
8B/01/68
Signed value.
If the PID regulator is to be controlled via a network, this reference must be written, in accordance with the protocol:
• Either via messaging
• Or by assigning this parameter in the periodic variables
AIU1
Parameter name:
 Network analog input
Terminal display:
[Network AI]
Logic address:
5281 = 16 #14A1
Type:
INT
CANopen index:
2016/52
Read/write:
R/W
INTERBUS index:
5FB9/43
Unit:
1
DeviceNet path:
7B/01/52
MFr
Parameter name:
Multiplying coefficient
Terminal display:
[Multiplying coeff.] 
Logic address:
11831 = 16#2E37
Type:
UINT
CANopen index:
2058/20
Read/write:
R/W
INTERBUS index:
5FB6/38
Unit:
1%
DeviceNet path:
9C/01/20
Code
Description