Status parameters
 
86
CCC
Parameter name:
Active command channel
Logic address:
8442 = 16#20FA
Type:
WORD (bit register)
CANopen index:
2036/2B
Read/write:
R
INTERBUS index:
5FB9/D3
DeviceNet path:
8B/01/2B
bit 0: = 1: The terminals are the active command channel
bit 1: Reserved (= 0)
bit 2: = 1: The graphic display terminal is the active command channel
bit 3: = 1: Modbus is the active command channel
bit 4: Reserved (= 0)
bit 5: Reserved (= 0)
bit 6: = 1: CANopen is the active command channel
bit 7: = 1: The terminals are the active command channel in +/- speed
bit 8: = 1: The graphic display terminal is the active command channel in +/- speed
bit 10: = 1: The "Controller Inside" card is the active command channel
bit 11: Reserved (= 0)
bit 12: Reserved (= 0)
bit 13: Reserved (= 0)
bit 14: Reserved (= 0)
bit 15: = 1: The PowerSuite software workshop is the active command channel
CFPS
Parameter name:
Active parameter set
Logic address:
12900 = 16#3264
Type:
WORD (listing)
CANopen index:
2063/01
Read/write:
R
INTERBUS index:
5FB9/EB
DeviceNet path:
A1/01/65
0 : The parameter set switching function is not configured
1 = 
[Set 1 active]
 
(CFP1)
: Parameter set no. 1 active
2 = 
[Set 2 active]
 
(CFP2)
: Parameter set no. 2 active
3 = 
[Set 3 active]
 
(CFP3)
: Parameter set no. 3 active
CNFS
Parameter name:
Active configuration
Terminal display:
[Config. Active]
Logic address:
8020 = 16#1F54
Type:
WORD (listing)
CANopen index:
2032/15
Read/write:
R
INTERBUS index:
5FB9/D1
DeviceNet path:
89/01/15
0 : The motor or configuration switching function is not configured
1 = 
(CNF0)
: Configuration no. 0 active
2 = 
(CNF1)
: Configuration no. 1 active
3 = 
(CNF2)
: Configuration no. 2 active
Code
Description