Chapter 3: Accessing the PM IPDU via the Command Line Interface        25
Examples
To set the ID of PM IPDU 1 R&D, enter:
To display the ID of PM IPDU 2, enter:
To rename an ID to “sammy,” using an existing ID “QA,” enter:
To display the IDs of all PM IPDUs in the daisy chain, enter:
interval
The interval command configures the time interval (in seconds) to turn on power for each outlet in 
the system. This command is available to the admin user only.
Syntax 
interval <outlet_number> <duration>
Arguments
NOTE: When this value is set to 0.0, there is still an interval of approximately 0.1 seconds between outlets to 
receive power.
Examples
To display the interval of outlet 1, enter:
To set the interval of outlets 2, 4, 5, and 6 to a value of 2.4, enter:
pm>id 1 R&D
pm>id 2
pm>id QA sammy
pm>id
<duration>
Sets the interval to turn on power to outlets. Valid intervals are 
from 0 to 100. Default value is 0.5
<outlet_number>
Outlet number, such as “5”, outlet name such as “sunfire”, or group 
of outlets such as “1, 3-5”
pm>interval 1
pm>interval 2,4-6 2.4