Carrier Access 1750 Manual De Usuario

Descargar
Página de 420
Broadmore 1750 - Release 4.6
2-13
 Planning 
and 
Ordering Guide
Installation Planning Factors
Installation Planning Factors
The Broadmore 1750 is designed and delivered ready for installation in a standard 19" 
or 23" relay or EIA equipment rack. Several factors should be considered and some 
decisions made to ensure a smooth installation that meets all requirements. Installation 
factors and system specifications are shown in the following tables.
Factor
Consideration
Access 
Clearance
Broadmore 1750 requires the following access clearances for 
service and maintenance: 
Front: 24" 
Rear: 4"
Top: 1.75" (Broadmore 1750 units may be stacked without this 
clearance.)
Power 
Source
DC Power: –48 VDC at 5 amperes is connected to the rear of the 
Broadmore chassis. A second –48 VDC source may be connected 
for redundancy. 
Optional AC Power Supply Tray: Converts 110/240 VAC (50-60 
Hz) to –48 VDC. Rack mounted tray (3.5" high) installs 
immediately below Broadmore chassis and can hold two power 
supplies. Unit comes with one power supply and cables. A second 
power supply with cables can be added to provide redundant DC 
power to the Broadmore. AC and DC power connections are at the 
rear of the unit. The DC cable is approximately 3.5 ft. long.