Carrier Access 770-0125-AB Manual De Usuario
BROADway - Release 4.00
2-7
Installation
Cabling Power and Ground
3. On the back of the chassis are two separate DC feeds (FEED A and FEED B).
Remove the green connector from the FEED A plug.
4. Attach the appropriate leads to the connector. Your power wires will originate from your DC
power source.
How you attach the leads varies based on whether you are using a -48 V DC ground referenced
power source, or a +24 V DC ground referenced power source.
power source, or a +24 V DC ground referenced power source.
CONNECTION INFORMATION
FOR +24VDC: 24V to +, RTN to -
FOR -48VDC: RTN to +, -48V to -
FOR +24VDC: 24V to +, RTN to -
FOR -48VDC: RTN to +, -48V to -
+24/-48 VDC, 10 A
THIS UNIT MAY CONTAIN A CLASS 1 LASER PRODUCT WHICH
CONFORMS TO THE APPLICABLE REQUIREMENTS OF 21 CFR
SUBCHAPTER J. REFER TO THE INSTALLATION MANUAL.
CONFORMS TO THE APPLICABLE REQUIREMENTS OF 21 CFR
SUBCHAPTER J. REFER TO THE INSTALLATION MANUAL.
FEED A
FEED B
CAUTION: THIS UNIT HAS MORE THAN ONE POWER SUPPLY CONNECTION.
DISCONNECT BOTH POWER SUPPLY CONNECTIONS BEFORE SERVICING TO
AVOID ELECTRIC SHOCK.
DISCONNECT BOTH POWER SUPPLY CONNECTIONS BEFORE SERVICING TO
AVOID ELECTRIC SHOCK.
OFF
O
POWER A
POWER B
ON
I
OFF
O
ON
I
Connect to Earth ground
Connect to +24VDC or -48VDC power source
BROADway Chassis Rear Panel View
BROADway
-48 VDC Feed
+
-
RETURN
-48 VDC
Ground at power source
Using a -48 VDC Power Source