Chapter 4: E2 Controller
4.9.5 Sensor Failure Packed Bit Variables
Table 4-33. Sensor Failure Packed Bit Variables.
Bit
Sensor Failures 1
Sensor
Failures 2
Failures 2
0
Middle temperature
Reserved
1
Upper temperature
Reserved
2
Lower temperature
Reserved
3
Return temperature
Reserved
4
Return humidity
Reserved
5
Static air pressure
Reserved
6
Suction pressure
Reserved
7
Suction temperature
Reserved
8
Discharge pressure
Reserved
9
Discharge temperature
Reserved
10
Remote temperature
Reserved
11
Remote humidity
Reserved
12
Entering water temperature
Reserved
13
Leaving water temperature
Reserved
14
Reserved
Reserved
15
Reserved
Reserved