BS-3680 THIN PLATE RECTANGULAR WEIR,  P3 = 6 
‘U’ parameters required *
‘U’ parameters calculated **
U0 = approach width 
B
U3 = Ce
U1 = crest width 
b
U4 = K
b
U2 = crest height 
p
*obtain from manufacturer’s specifications.
**
calculated by OCM-3. May be viewed by accessing ‘U’ parameter.
Reference
ABSOLUTE CALCULATION,  P4 = 0
¤
 
For flows that can be calculated by the equation:
q
 
= 
Ce
 
x
 
2
3
 
√⎯⎯⎯
2
g
  
x
 
be
 
x
 
(
h
e
)
1.5
where :  q = flow rate
Ce = a function of h, p, b and B
g = gravitational acceleration
be = effective crest width (b + K
b
)
b = crest width 
h
e
 = effective head (h + K
h
)
h = head
K
h
 = 1 mm
RATIOMETRIC CALCULATION,  P4 = 1
¤
 
For flows that can be calculated by the equation:
q = q
cal
 x Ce/Ce
cal
 x (h/h
cal
)
1.5
where :
q = flow rate
q
cal
 = flow rate at maximum head
h = head
h
cal
 = maximum head
Ce = discharge coefficient for head
Cv
cal
 = discharge coefficient for maximum head
¤
 Refer to Operation \ Flow Calculation.
7ML19985AB01
OCM III
68