12.2 Troubleshooting Flowchart
12.2.5 Flowchart for when the "RUN" LED turns off
12
TROUBLESHOOTING
12.2.5  Flowchart for when the "RUN" LED turns off
The following shows the flowchart for when the "RUN" LED of 
the CPU module turns off during operation of the programmable controller.
Figure 12.4 Flowchart for when the "RUN" LED turns off
YES
NO
The "RUN" LED has turned off.
Completed
Does the "RUN" LED 
turn on?
How 
is the "POWER" 
LED of the power supply 
module?
Is the "ERR." LED 
on/flashing?
Off
On
Section 12.2.3 Flowchart for when 
the "POWER" LED turns off
Section 12.2.7 Flowchart for when 
the "ERR." LED is on/flashing
YES
YES
NO
Reset the CPU module 
RUN/STOP/RESET switch.
Set the CPU module 
RUN/STOP/RESET switch to STOP.
Write END to sequence step 0 with 
GX Developer.
Set the CPU module 
RUN/STOP/RESET switch to RUN.
Is the 
operation monitored 
by GX Developer 
possible?
Possible cause is a sequence 
program error.
Check the program and modify 
the program error location.
Has 
measures been 
taken against noise?
Take measures against noise.
Possible cause is a 
programmable 
controller part fault/poor connection.
Please consult your local Mitsubishi 
representative, explaining a detailed 
description of the problem.
NO
YES
NO
Replace the CPU module.