Emerson MODBUS IP Manual De Usuario
BACnet Communications - Thermal Management Products
227
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 78
Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Analog Data
Data Label
Object Type
Instanc
e
Object Name
Acces
s
Notes
Extra
Notes
Air
Air Temperature Set Point
Analog_Value
1
5008_1
RW
Units: deg C
1, 2, 3,
4, 5, 6
Air Temperature Set Point
Analog_Value
10001
5008_1_deg_F
RW
Units: deg F
1, 2, 3,
4, 5, 6
Air Temperature Proportional
Band
Analog_Value
2
5325_1
RW
Units: deg C
1, 2, 3,
4, 5, 6
Air Temperature Proportional
Band
Analog_Value
10002
5325_1_deg_F
RW
Units: deg F
1, 2, 3,
4, 5, 6
Air Temperature Dead Band
Analog_Value
3
5011_1
RW
Units: deg C
1, 2, 3,
4, 5, 6
Air Temperature Dead Band
Analog_Value
10003
5011_1_deg_F
RW
Units: deg F
1, 2, 3,
4, 5, 6
Air Temperature Control
Integration Time
Analog_Value
4
5326_1
RW
Units: min
1, 2, 3,
4, 5, 6
Today's High Air Temperature
Analog_Value
5
5327_1
RD
Units: deg C
1, 2, 3,
4, 5, 6
Today's High Air Temperature
Analog_Value
10005
5327_1_deg_F
RD
Units: deg F
1, 2, 3,
4, 5, 6
Today's High Air Temperature
Time
Analog_Value
6
5328_1
RD
Units: Seconds
since Midnight
1, 2, 3,
4, 5, 6
Today's Low Air Temperature
Analog_Value
7
5329_1
RD
Units: deg C
1, 2, 3,
4, 5, 6
Today's Low Air Temperature
Analog_Value
10007
5329_1_deg_F
RD
Units: deg F
1, 2, 3,
4, 5, 6
Today's Low Air Temperature
Time
Analog_Value
8
5330_1
RD
Units: Seconds
since Midnight
1, 2, 3,
4, 5, 6
Air - Supply Air
Supply Air Temperature
Analog_Value
19
5002_1_1
RD
Units: deg C
1, 2, 3,
4, 5, 6
Supply Air Temperature
Analog_Value
10019
5002_1_1_deg
_F
RD
Units: deg F
1, 2, 3,
4, 5, 6
Supply Air Temperature Set
Point
Analog_Value
20
5331_1_1
RW
Units: deg C
1
Supply Air Temperature Set
Point
Analog_Value
10020
5331_1_1_deg
_F
RW
Units: deg F
1
Supply Air Over Temp Threshold
Analog_Value
21
5014_1_1
RW
Units: deg C
2, 3, 4,
5, 6
Supply Air Over Temp Threshold
Analog_Value
10021
5014_1_1_deg
_F
RW
Units: deg F
2, 3, 4,
5, 6
Supply Air Under Temp
Threshold
Analog_Value
22
5018_1_1
RW
Units: deg C
2, 3, 4,
5, 6
Supply Air Under Temp
Threshold
Analog_Value
10022
5018_1_1_deg
_F
RW
Units: deg F
2, 3, 4,
5, 6
Air - Return Air
Return Air Temperature
Analog_Value
31
4291_1_1
RD
Units: deg C
1, 2, 3,
4, 5, 6
Return Air Temperature
Analog_Value
10031
4291_1_1_deg
_F
RD
Units: deg F
1, 2, 3,
4, 5, 6
Return Air Temperature Set
Point
Analog_Value
32
5333_1_1
RW
Units: deg C
1