Emerson 10-30kVA Manual De Usuario

Descargar
Página de 80
UPS Specifications
41
6.4.4 Inverter Output
6.4.5 Bypass Input
Table 14
Inverter output
Rated Power
10kVA
15kVA
20kVA
30kVA
Rated voltage, VAC
120/208
Supply
3-phase, 4-wire plus ground
Frequency, Hz
 50 / 60
Rated Power, kW
8
12
16
24
Three -phase transient overload,
min. load
10 minutes - 105-125% load
1 minute - 126-150% load
Voltage Regulation %
±1.0% three-phase RMS average for a balanced three-phase load
±2.0% three-phase RMS average for a 100% unbalanced load
Frequency Regulation %
Nominal frequency regulation is ±0.05% in single module mode,
and+/- 0.25% in parallel mode.
Maximum rate of change of 
frequency, Hz/sec
For single mode, the slew rate is adjustable from 0.1Hz/s to 3Hz/s
Current rating of neutral cable, A
1.5 x input current
Table 15
Bypass input
Rated Power
10kVA
15kVA
20kVA
30kVA
Rated voltage, VAC
120/208
Supply
Three-phase, 4-wire plus ground
Rated Current, A
208VAC
28
42
56
83
Bypass voltage tolerance %
Upper limit: +10%, +15% or +20%
Lower limit: -10%, -20%, -30% or -40%
Upper limit default: +15%
Lower limit default: -20%
Frequency, Hz
50 / 60
Input frequency tolerance %
± 10 or ± 20%; default ±10%
Current rating of neutral cable, A
1.5 x input current
Bypass overload capacity
(all ratings)
Time
Long-term operation:
10 minutes:
100milliseconds:
Load
<135% load
135% - 170% load
1000% full UPS rated output current