 Installation 
Guide 
SG Series 225 & 300 kVA 
4.1.7  EPO (Emergency Power Off) Input contact 
 
SGS_225-300_C
ustomer interfac
e EPO_01
4
3
2
1
1
2
3
4
JP3
XB
J2
 
Fig. 4.1.7-1   Terminals for connection EPO
 
An external Emergency switch 
(Normally Closed voltage-free 
contact) can be connected on 
terminals  XB / 1 - 4 or connector 
J2 / 12 - 25  of the P4 - Interface 
Customer

 
 
 
Remove the cable short-
circuiting terminals XB 2 - 3) 
when using this external switch.
 
 
To enable this function, remove cable short-circuiting XB / 2 - 3 on the 
Terminal XB and the Jumper JP3 on P4 – Customer Interface
, when the 
cables have been already connected on XB or J2
 
 
In a parallel system a separate NC (Normally Closed) contact must be 
connected individually to each unit.
 
 
When opened, this contact causes the immediate opening of the Contactors K3K4K6K7 
and K8
, as well as the shutdown of RectifierInverter and Static-Switch
 
 
Be aware: The reliability of the system depends on this contact! 
 
After closure of the Emergency contact, a reset is necessary to enable the restart of 
the UPS, by pressing the key “O”
 (inverter off) on the control panel. 
 
 
In case of a parallel system press the key “O” (inverter off) on the 
control panel of each unit connected on parallel bus and having it’s 
output switch Q1 closed.