OPM_MLE_LTE_350_1K0_1GB_V011
 
2
 
DE ML Series: user manual 1.1 (GB)
 
GE Digital Energy
 ML Series
g
 
 
 
 
 
1.1 Introduction 
 
The GE (General Electric) Digital Energy™ ML Series UPS, an uninterruptible power supply, protects 
your equipment from all forms of power interference, including complete power failures. 
 
 
1.2 Safety 
Rules 
 
 
 
CAUTION:
  RISK OF ELECTRICAL SHOCK. The UPS contains batteries. The 
appliance outlets may be electrically live, even when the UPS is disconnected from the 
mains. 
 
  The UPS contains potentially hazardous voltages. Do not open the UPS, there are no 
user serviceable parts inside. 
 
  Apart from battery replacement on the ML 350/500/700 models, all maintenance and 
service work should be performed by qualified service personnel. 
 
  Always isolate the UPS from the mains during battery replacement. 
 
1.3 
Transport / Storage 
 
 
  No liability can be accepted for any transport damage when the equipment is shipped in non-
original packaging. 
 
  Before storing, charge the batteries for at least 24 hours. 
 
  Store the UPS in a dry location, storage temperature must be within -20 +45 
°
C. If the unit is 
stored for a period exceeding 3 months, optimal battery lifetime is obtained if the storage 
temperature does not exceed 25
°
C. Be sure that the UPS is switched off, and that no cable is 
connected to the interface port. 
 
  If the unit is stored for a period exceeding 3 months, the batteries must be recharged 
periodically. Connect the unit to a wall outlet for a period of approx. 48 hours, minimum every 3 
months. 
 
 
 
 
 
The shipping box contains a Digital Energy™ ML Series UPS, a power cord, a computer interface 
cable, a CD ROM and this manual. After unpacking, inspect the UPS for damage. If you find any damage 
please immediately notify the carrier and place of purchase. 
 
IMPORTANT
Before making any connection and switching on the Digital Energy™ ML Series UPS, please check the 
following conditions: 
 
 
  your mains supply is 220 - 240 Volts and 50 Hz, and 
 
  the total power demand of the connected equipment does not exceed the rated output power of 
the UPS (indicated on the rear panel). 
 
2.1 Installation 
Rules 
 
 
  The UPS is intended to be used in normal domestic and office situations. 
 
  Protect the UPS, according to the wiring rules, with a 16A D-type fuse. 
 
  The UPS must be powered from a single phase grounded wall outlet. Do not use extension 
cords. 
 
  Avoid locations that are excessively humid, near water, near heat sources or in direct sunlight. 
 
  The ambient temperature should not exceed 40
°
C. Optimal battery lifetime is obtained if the 
ambient temperature does not exceed 30
°
C. 
 
  It is important that ventilation air can move freely around and through the unit. Do not block the 
air vents. 
 
  Do not plug appliances such as electric heaters, toasters and vacuum cleaners into the UPS. 
The UPS output can be used only for electronic loads such as computers and 
telecommunications equipment. 
 
  Be careful when connecting laser printers: be sure that the demanded power does not exceed 
the capacity of the UPS. 
 