ACCEPTANCE TESTS 
 
GEK-106465A 
CIO Remote CAN Digital I/O Module  
 41
 
6.6. COMMUNICATION 
WITH THE MASTER UNIT 
1.  Connect the master unit to the CIO. Verify that the BUS LED blinks indicating communication between both 
units. 
2.  Verify, using the master unit Setup program, that the CIO boards setting options are available. For example, 
using an F650 as master unit, verify in EnerVista F650 Setup, that the "Actual > Inputs/Outputs > I/O 
Board Status > Board H Status
" and "Actual > Inputs/Outputs > I/O Board Status>Board J Status
appear as active. 
 
6.7. 
INPUTS AND OUTPUTS 
During all tests, the screw on the rear of the relay must be grounded. 
6.7.1. DIGITAL 
INPUTS 
During this test, the user will determine the activation/deactivation points for every input in the relay for the set voltage 
value of 30 Volts. 
Verify that the error does not exceed +/- 10% (+10% on activation, -10% on deactivation) 
Default board settings for the input test are as follows: 
Settings/Control Elements/Inputs Outputs/Board X 
 
I/O Board Type 1 
 
Voltage Threshold A_01 
30 V 
Voltage Threshold B_01 
40 V 
Debounce Time A_01 
15 ms 
Debounce Time B_01 
15 ms 
Input Type 01 00 (CC1) 
POSITIVE 
... ... 
Input Type 01 15 (CC16) 
POSITIVE 
 
The inputs test is completed by groups of 8 inputs, as this type of board has 2 groups of 8 inputs with the same 
common. For the first 8 inputs, the voltage threshold setting is determined by Voltage Threshold A. For the next 8 
inputs, the setting is Voltage Threshold B. 
Inputs (or contact converters, CC1 – CC15) must also be set to POSITIVE. 
I/O Board Type 2 
 
Voltage Threshold A_01 
30 V 
Voltage Threshold B_01 
40 V 
Debounce Time A_01 
5 ms 
Debounce Time B_01 
5 ms 
Input Type 01 00 (CC1) 
POSITIVE 
... ... 
Input Type 01 07 (CC8) 
POSITIVE