A016: 
External Frequency Filter Time Constant – This filter smooths the analog input signal 
for the inverter’s output frequency reference.
• A016 sets the filter range n=1 to 16. This is a simple moving average calculation, 
where n (number of samples) is variable.
• A016 = 17 is a special value. It configures the inverter to use a moveable deadband 
feature. Initially the inverter uses the average of the previous 16 samples. Then, the 
deadband is employed for each subsequent average of 16 samples. The deadband 
works by ignoring small fluctuations in each new average: less than +0.1Hz or –0.2Hz 
change. When a 16-sample average exceeds this deadband, then the inverter applies 
that average to the output frequency reference, and it also becomes the new deadband 
comparison point for subsequent sample averages.
“A” Function
Run 
Mode 
Edit
Lo Hi
Defaults
Func.
Code
Name /
SRW Display
Description
–FE(F) 
(EU)
–FU 
(USA)
Units
A005 [AT] selection
Four options, select codes:
00 .. Select between [O] and 
[OI] at [AT]
01 .. [O] + [OI] ([AT] input is 
ignored)
02 .. Select between [O] and 
keypad potentiometer
03 .. Select between [OI] and 
keypad potentiometer
✘ ✔
00
00
Hz
AT-Slct    O/OI
A011 O–L input active range 
start frequency
The output frequency corre-
sponding to the analog input 
range starting point,
range is 0.0 to 400.0
✘ ✔
0.0
0.0
Hz
O-EXS   0000.0Hz
A012 O–L input active range 
end frequency
The output frequency corre-
sponding to the analog input 
range ending point,
range is 0.0 to 400.0
✘ ✔
0.0
0.0
Hz
O-EXE   0000.0Hz
A013 O–L input active range 
start voltage
The starting point (offset) for 
the active analog input range,
range is 0. to 100.
✘ ✔
0.
0.
%
O-EX%S    00000%
A014 O–L input active range 
end voltage
The ending point (offset) for 
the active analog input range,
range is 0. to 100.
✘ ✔
100.
100.
%
O-EX%E    00100%
A015 O–L input start 
frequency enable
Two options; select codes:
00 .. Use offset (A011 value)
01 .. Use 0 Hz
✘ ✔
01
01
O-LVL      0Hz
A016 External frequency 
filter time constant
One range plus one setting:
01 to 16...  Moving average, 
where n=1 to 16 (number of 
samples for average)
17 .. Use 16-sample average, 
plus deadband +0.1/–0.2Hz.
✘ ✔
2.
8.
Sam-
ples
F-SAMP     00008