12/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
3.2 OPERATION 
MODES 
3.2.1  Normal operation mode 
During normal operation, the Rectifier 
converts input AC power to DC. 
The DC power provides input power for the 
Inverter and charging power for the Battery
The  Inverter converts the DC power to 
continuous and regulated AC power, which 
supplies the critical load. 
The control panel reports the Battery charge 
status and the expected backup time with the 
actual load. 
Fig. 3.2.1-1   Block diagram normal operation mode 
 
 
 
3.2.2  Utility failure operation 
When the Utility is no longer within acceptable 
tolerances, the Battery will provide the DC 
power to the Inverter
The  Inverter will maintain continuous AC 
power to the Load until the Battery Voltage 
reaches the lower limit of the Inverter 
operation capability. 
During the discharge, the LCD screen displays 
the estimated time the Battery can support the 
critical load. 
Prior to the Battery completely discharging, 
the  "stop operation" alarm (shutdown 
imminent) warns the operator that the Battery 
is almost discharged and the UPS is about to 
shut down. 
Fig. 3.2.2-1   Block diagram Utility Failure operation
 
 
   In case of parallel operation 
 
With a parallel system for power capacity (see Section 3.3) 
• 
With the Bypass Utility power available, a low Battery warning on any unit will cause the 
Load to be transferred to Utility (after a selectable time delay). 
• 
With  Bypass Utility power not available, a low Battery warning on any unit will start the 
stop operation” timer (adjustable). 
The Load will shut down at the end of the “stop operation” time period. 
 
With a parallel system for redundancy (see Section 3.3) 
• 
When a Battery low warning occurs on a unit not necessary to support the present load, this 
unit will shut down after a timeout period (selectable). 
The Load is shared between the other units 
• 
As the warning occurs on one unit necessary to support the present load, the system starts 
the "stop operation" timeout (selectable). 
The Load will shut down at the end of the “stop operation” time period.