GE 30 Manual De Usuario

Descargar
Página de 88
 
GE
 
OPM_SGS_USM_10K_40K_0US_V010.doc 
23/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
6.1 METERING 
MODE 
The metering mode is entered any time the metering button is pressed. 
While in this mode the LCD will display a series of screens containing metering information. 
In this mode the buttons perform the following functions: 
metering 
Scrolls forward to the next screen. 
alarms Abandons 
the 
metering mode  and enters the alarms mode
parameters Abandons 
the 
metering mode and enters the parameters mode
+ 
Scrolls forward to the next screen. 
 
Scrolls backward to the previous screen. 
ok 
Displays the main screen for this mode. 
 
Main screen 
This screen displays the current status of the UPS in a condensed form. 
The information offered by this screen consists of: 
• 
The type of the machine: Family name, series number (P + unit number for parallel 
version from 1 to 8) and power range. 
• 
The status of the load. 
• 
The Load amount as a percentage of the nominal Load (referred to the most loaded phase).
 
• 
The estimated Battery backup time in minutes with the present load.
 
 
 
SG Series  S0  30kVA 
LOAD ON INVERTER 
 
LOAD  =  84% 
Autonomie = 12min
 
metering
alarms
parameters
+
ok
 
 
Battery data screen 
This screen displays: 
• 
The Battery voltage. 
• 
The Battery Current (negative values correspond to the discharge of the Battery). 
• 
The temperature of the Battery (XXX indicates sensor disabled).
 
• 
The current charge level.
 
• 
The estimated backup time with the present load.
 
 
Ub=540V   Ib=  + 15A 
  Battery  Temp=  + 20
°
 Charge  Level=  87% 
 Autonomy  =  12min 
metering
alarms
parameters
+
ok
 
 
Bypass Utility data screen 
This screen refers to the AC source supplying the Bypass. This screen displays: 
• 
The frequency.
 
• 
The voltage levels of the three phase voltages.
 
 
U TILIT Y  
f = 60.0 H z 
U 1=2 76V       U 2=27 5V  
U 3= 277V  
m eterin g
alarm s
 
pa ram eters
+
ok