OPM_SGS_USM_10K_40K_0US_V010.doc 
32/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
6.5 USER 
PARAMETERS 
Pressing the Parameters button displays a series of screens containing the user parameters 
on the LCD panel
This first parameter level in not protected by password, therefore the user can freely adapt 
these parameters to their needs. 
The meaning of the user parameters and their use is described below (buttons performance is 
described to Section 6.3). 
 
1.  Date and Time set-up 
DATE AND TIME 
D   M   Y 
   Date:    01.09.2002 
   Time:    19:44:07 
metering
 
alarms
 
parameters
+
ok
 
Date 
You can adjust the date of the real time clock existing in the UPS by the means of this 
parameter. 
The value you enter is thoroughly checked to be a correct date in the format 
“dd.mm.yy”. 
 
Time 
You can adjust the time of the real time clock existing in the UPS by means of this 
parameter. 
The value you enter is thoroughly checked to be a correct time in the format 
“hh.mm.ss”. The time is specified in 24-hour format. 
 
 
 
2. Protocol 
Set-up 
PR O TO C O L  SETU P 
M odem  enabled= N  
Init= BEQ V1X3&D 0S0=2
Alarm =N   D elay=22sec 
m etering 
alarm s 
param eters 
+
ok
 
Modem enabled 
You can enable/disable with Y/N the remote control through modem calls 
by using this parameter. 
 
Init 
This parameter presents the modem initialization string. 
 
It can be 39 characters long. 
 
When editing this parameter the UPS considers that a blank character 
terminates the string. 
 
If no blank character is found then all 39 characters are used. 
 
Alarm This 
Y/N parameter controls the automatic events signaling through 
modem. 
 
If this parameter is set to Yes the UPS itself will call the remote location 
when a new event occurs. 
 
Delay 
This parameter controls the delay between the occurrence of a new event 
and the modem dialing. 
 
It is useful because since the events typically do not occur isolated but in 
certain sequences, you can eliminate the need for multiple dial-outs for 
such a sequence of events.