35/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
6.6  EVENTS (ALARMS AND MESSAGES) 
 
Each of the following listed events can be displayed on the LCD screen or on PC where the 
ARGUS/JumpManager - Control Network is installed. 
 
Alarms and Messages are differently specified because the alarms are indicating an 
abnormal functioning of the UPS (which are additionally signaled with the LED alarm and 
acoustically with the buzzer), while the messages indicate the various states of operation of 
the UPS (stored in the events list, but no activating the LED alarm and the buzzer). 
 
When in the alarms mode, the LCD screen displays a time ordered sequence of 
screens corresponding to the last 256 alarms and messages, each screen indicating: 
 
The number of the event (255 = the most recent). 
The date and time when the event occurred. 
The standard code and the status word.
An explicit text description of the events.
 
 
6.6.1 Alarms 
list 
 
Code 
Alarms 
Meaning 
4000 
SETUP VALUES 
LOST 
Parameters are lost and have been replaced with default 
values. 
Call nearest Service Center for intervention. 
4004 
UPS 
FAILURE 
The master unit detected the slave unit missing on the 
communication bus even though switch Q1 is still closed. 
4100 
RECTIFIER FUSES 
FAILURE 
The u-switch mounted on the Rectifier Input Fuses indicates 
a blown fuse, and consequently shut down. 
Clearance of this condition allows you to restart the Rectifier
4102 
K4 CLOSING 
FAILURE 
K4 not closed despite a closing command being issued. 
Signaled by auxiliary contact. 
Rectifier cannot start. 
4103 
K4 OPENING 
FAILURE 
K4 not open despite an opening command being issued. 
Signaled by auxiliary contact. 
Utility remains connected to Rectifier bridge
4104 
BATTERY 
FUSES 
This function, when enabled on input programmable relays 
(password required), warns the user about the external 
Battery Fuses failure or MCB opening, signalled by NO free 
contact. 
4105 
RECTIFIER 
OVERTEMPERATURE 
Temperature sensor indicates an over temperature on the 
Rectifier Bridge
Only alarm is given. 
The Rectifier, when in Off state, cannot start as long as this 
condition persists. 
4106 
RECTIFIER 
TRANSFORMER 
OVERTEMPERATURE 
The temperature sensor inside the input transformer winding 
indicates over temperature. 
Only the alarm is given. 
The Rectifier, when in Off state, cannot start as long as this 
condition persists. 
4110 
RECTIFIER UTILITY 
OUT OF TOLERANCE 
Rectifier Input Utility is out of tolerance (voltage, frequency or 
phase).