79/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
8 CUSTOMER 
INTERFACE 
8.1 CUSTOMER 
INTERFACE 
Serial port J3 - RS 232 (sub D - female 9 pin) 
Suitable for JUMP protocol 
Pin 2: TX (out)                     Pin 3: RX (in)                     Pin 5: GND 
 
J2 (subD-female 25p) – Output signals on voltage free contacts
J2/1, 2, 3 
- NO, 
C, 
NC 
- Utility Failure 
(def. Param. RL=1)
J2/4, 5, 6 
- NO, 
C, 
NC 
- Load on Inverter  (def. Param. RL=3)
J2/7, 8, 9 
- NO, 
C, 
NC 
- Stop Operation 
(def. Param. RL=5)
J2/14, 15, 16  - NO, 
C, 
NC 
- Load on Utility 
(def. Param. RL=2)
J2/17, 18, 19  - NO, 
C, 
NC 
- General Alarm 
(def. Param. RL=4)
J2/20, 21, 22  - NO, 
C, 
NC 
- Acoustic Alarm 
(def. Param. RL=6)
 
Signals on terminals X1 and on connector J2 are in parallel 
and therefore not separated galvanically from each other. 
The programmable signals on X1 and J2 will be disabled with Q1 
open, with the exception of the signals for “16 - Manual Bypass ON”
 
and “26 - EPO”
 
XB - Terminals for EPO connection
 
X2 / 1, 2 or J2 / 12, 25
 
NC
 
EPO
 (Emergency Power Off)
 
Note: to enable this function, remove cable short-circuiting XB / 2 – 3 
and the Jumper JP3 on P4 – Customer Interface.
 
 
X1 – Output signals on voltage free contacts - terminals 
X1/1, 2, 3 
- NO, 
C, 
NC  - Utility Failure 
(def. Param. RL=1)
X1/4, 5, 6 
- NO, 
C, 
NC  - Load on Inverter 
(def. Param. RL=3)
X1/7, 8, 9 
- NO, 
C, 
NC  - Stop Operation 
(def. Param. RL=5)
X1/12, 13, 14  - NO, 
C, 
NC  - Load on Utility 
(def. Param. RL=2)
X1/15, 16, 17  - NO, 
C, 
NC  - General Alarm 
(def. Param. RL=4)
X1/18, 19, 20  - NO, 
C, 
NC  - Acoustic Alarm 
(def. Param. RL=6)
 
Input contacts 
X1/10, 21 or J2/10, 23  Programmable (default = RL1) 
X1/11, 22 
or J2/11, 24  Programmable / Generator ON (NO) (def. = RL2) 
1
12
13
2
14
3
15
4
16
5
17
6
18
7
19
8
20
9
21
10
22
11
1
14
9
1
X1
J2
J3
SGT5000_100-150_Cus
tomer int
er
fa
ce_
01
J5
J4
XA
2
1
XB
1
2
3
4
1
2
3
4
JP3
 
Fig. 8.1-1   Customer interface
 
NO = normally open           C = common          NC = normally closed
 
The connectors J4 and J5 can be used for additional SNMP CardEnvironmental Card (not available yet)
or an additional Customer Interface (installation only when the UPS is switched Off). 
XA: terminals for 24VDC Auxiliary Power Supply connection.                     XB: terminals for EPO connection.
 
Programmable user relays 
Programmable functions on contacts (X1 - J2) 
On terminals X1  or  J2  connector, six of the following 26 
signals
 can be selected from the display, entering with the 
appropriate password
  0- No Information 
  1- Buzzer 
  2- General Alarm 
  3- Load on Utility 
  4- Stop Operation 
  5- Load on Inverter 
  6- Utility Failure 
  7- DC Over Voltage 
  8- Low Battery 
  9- Overload 
10- Over Temperature 
11- Inverter-Utility not syncr. 
12- Bypass Locked 
13- Bypass Utility Failure 
14- Rectifier Utility Failure 
15- Battery Discharge 
16- Manual Bypass ON 
17- Rectifier ON 
18- Inverter ON 
19- Boost Charge 
20- Battery Earth Fault 
21- Battery Fault 
22- Relay Input 1 
23- Relay Input 2 
24- Relay Output ON 
25- Relay Output OFF 
26- EPO (Emergency    
Power Off) 
Some UPS functions can be activated with 
parameters when an external Normally Open 
contact is closed on: 
X1-10, 21 / J2-10, 23    or   X1-11, 22 / J2- 11, 24 
 
Selectable functions by changing parameters 
(password required) are: 
0 - No function  
1 - Inverter ON 
2 - Inverter OFF 
3 - Print All 
4 - Status Relay 
5 - Generator ON 
6 - External Bypass ON 
7 - External Battery Fuses, or External K3. 
See Alarm 4104 - “Battery Fuses”. 
 
Voltage free contacts:  Max. DC / AC: 24V / 1.25A 
   IEC 950 (SELV circuit) 
   Min. Signal Level: 5VDC/50mA