10.1.5  Long shut-down periods of the UPS-system 
To guarantee that the Battery is fully charged, the UPS system should be in operation for at least 
12 hours every 3 months
 
If not the Battery may be permanently damaged. 
 
 
 
 
10.1.6  UPS room conditions and temperature 
The UPS room and the Battery Room have to be maintained clean and free from dust. 
 
 
A high temperature of the UPS room and of the Battery Room affect the lifetime of several 
components inside the equipment. 
 
The Battery is very sensitive to room temperatures above 77°F (25°C). 
 
 
 
 
10.1.7  Long shut-down periods of the UPS-system 
a)   Cleaning, a visual inspection and a mechanical inspection of the UPS modules. 
 
b)
  Replacement of defective parts or the preventive replacement of parts with a defined lifetime 
 
c)
  “Updating” of the equipment (technical improvements subsequent to the delivery). 
 
d)
  Check the calibration of DC voltage and Inverter Output Voltage and Frequency
 
e)
  Check of the settings of the electronic regulation, the control and the alarm circuits of the 
Rectifier(s) and Inverter(s)
 
f)
   Functional checks on ThyristorsDiodesTransformersFilter Components, e.g. to ensure that 
they are operating within the specified design parameters. 
 
g)
   Overall performance test including a Utility Failure simulation with and without the Load
 
h)  Monitoring  Battery operation in discharge and recharge mode including any boost charge 
duties.