14/38 Installation 
Guide 
SG Series 225 & 300 kVA 
 
In case of parallel system, try to 
place the UPS modules in 
sequence of their numbers 
(marked on the packing). 
 
If the units are positioned “side 
by side
”, the side panels must be 
mounted on all units. 
UPS 1
UPS
3-4-5-6-7-8
UPS 2
S
G
S
_225-300_RP
A
 d
is
p
os
ition_G
E
_01US
Fig. 3.4.1-5   RPA system disposition
 
 
 
 
 
 
 
3.4.2 Battery 
location 
 
Batteries require a well-ventilated room with controlled temperature to obtain reliable 
operation. 
 
The  Battery can be install immediately adjacent to the UPS (left or right side) or remotely 
from the UPS. 
If the Battery is installed remotely from the UPS, a wall mounted DC disconnect device must 
be installed within line-of-site to both the UPS and the Battery
 
The optimal room temperature for the Battery
 is 68°F (20°C) to 77°F (25°C). 
 
The life of valve-regulated batteries will be reduced by 50% for each additional 18°F (10°C) 
that the Battery ambient temperature is above 77°F (25°C). 
 
The Battery System associated with larger UPS is usually either rack mounted or installed in 
multiple Battery Cabinets
 
Installation and assembly must be made according to the local standards and Battery 
System
 manufacturer‘s recommendations. 
 
The Battery Circuit Breaker or Battery Fuse Box must be mounted as near as possible to the 
Battery
 
 
 
Battery installation and connection must be performed by qualified 
personnel only. 
Read all safety instructions before proceeding with the installation.