GE Power Supply Manual De Usuario

Descargar
Página de 21
 
OPM_GTU_19X_1K0_3K0_XUS_V014
 
20
 
GT-UL Series: User manual 1.2 (US)
 
Digital Energy
 GT Series
g
 
 
 
 
 
GT Model 
 
1000R UL 
1500R UL 
2200R UL 
3000R UL 
Capacity 
 1kVA/800W 
1.5kVA/1200W 
2.kKVA/1600W 
3kVA/2400W 
Rated Voltage 
100V, 110V, 120V 
Voltage Range 
80V~138V (full load); 65V~80V (70% load) 
Frequency 
50Hz / 60Hz (± 4.8 Hz) 
Input 
Power Factor 
≥0.97 
Voltage 
100V, 110V, 120V 
Frequency 50Hz 
60Hz 
Voltage Regulation 
± 2% 
Frequency Accuracy 
± 0.05 Hz 
Wave Form 
pure sine wave 
Transient Response 
± 8% (10%~90% linear load) 
THD (linear load) 
≤3% 
≤3% 
≤3% 
≤4% 
THD (computer load) 
≤6% 
Overload Capacity 
105%~125% for 3mins; 125%~150% for 30secs; >150% for 1sec 
Crest Factor 
3:1 
Output 
Efficiency (AC-AC) 
≥ 87% 
Outlet 
Receptacle NEMA 
TYPE 
Battery Voltage 
36V 
48V 
48V 
72V 
Battery Type (Lead 
acid) 
12V/7Ah 12V/9Ah 
Back-up Time 
(Typical) 
5mins 
 
Battery 
Recharge Time 
4~6 hours after complete discharge to recover 90% 
Transfer 
Time 
Transfer Time 
zero 
LED Status 
On-line / Bypass / On-battery / Overload / Battery Low / Fault 
Battery Replace / Battery Level / Load Level 
LED 
Alarm buzzer 
DB9 RS232/dry 
contact 
Interface 
SNMP Slot 
internal 
Noise (At 1 Meter) 
40dB(A) 
45dB(A) 
45dB(A) 
47dB(A) 
Operating 
Temperature 
0~40°C (32~104°F) 
Environ-
ment 
Humidity 0%~90% 
(non-condensing) 
Safety UL/cUL 
EMC 
FCC Class A (1.5, 2.2, 3kVA) /B (1kVA) 
CISPR PUB 22 Class B; TUV/EMC; CE (1, 1.5kVA) 
CISPR PUB 22 Class A (2.2, 3kVA) 
Safety 
Approval 
Lightning IEEE 
62.41 
Category 
Battery Start 
yes 
Extended Battery 
Bank 
yes (optional for longer runtime) 
Others 
Long Time Model 
yes (optional) 
Dimensions 
(W
×D×H) 
440x434x88 mm 
17.3x17.1x3.4 inch 
440x526x88 mm 
17.3x20.7x3.4 inch 
440x503x132 mm 
17.3x19.8x5.2 inch 
Appearance 
Weight 
17kg 
37.4 lbs 
19kg 
41.8 lbs 
24kg 
52.9 lbs 
33 kg 
72.7 lbs 
 
All specifications are subject to change without prior notice. 
 