SMC Networks SMC 5000A Manual De Usuario

Descargar
Página de 96
SMA 
Technologie AG
Technical Data 
Installation Guide
SMC50A_60A-IEN073320
Page 77
Efficiency Curve of the SMC 5000A
The efficiency of the Sunny Mini Central depends mainly on the input voltage of the
connected PV strings. The lower the input voltage, the higher the efficiency.
Efficiency
Max. efficiency
ηmax
96,1 %
CEC rebate efficiency
euro
95,2 %
Weight
Weight
approx. 62 kg
a)
The Sunny Mini Central can temporarily feed power into the grid with a
maximum output voltage of 260 V. However, DIN VDE 0126-1-1 stipulates that
the average voltage over 10 minutes must not exceed 253 V. That means for
example, if the grid voltage is constantly 254 V, the inverter disconnects itself
from the grid. In this case, contact the local grid operator for assistance. 
DIN VDE 0126-1-1 only applies in Germany. See section 14.4.3 "Country-
specific Parameter Settings" (Page 89) 
for all other preset country values of
your inverter.
Description
Short 
descr.
Setting
Output power [W]
Ov
erall ef
fi
ci
ency
 [%]