SMA 
Technologie AG
Technical Data 
Installation Guide
SMC50A_60A-IEN073320
Page 89
14.4.3 Country-specific Parameter Settings
Sunny Mini Central SMC 5000A
The parameters listed below represent country-specific settings and are only displayed
in installer mode. All other parameters are international and can be viewed in the table
in section 14.4.2. 
Parameters designated with * are safety-related grid monitoring parameters. To
change the SMA grid guard parameters, you must enter your personal SMA grid
guard password (Inst.-Code). Call the SMA Serviceline to obtain your personal
SMA grid guard password.
You can see the default settings of the Sunny Mini Central on the name plate (see
section 4.1 "Identification" (Page 12))
.
Name
Short 
descr.
Country settings
Germany
Australia
Great
Britain
Italy
Spain
ACVtgRPro
V
253
253
253
253
253
Default
GER/
VDE0126-1-1
AUS/
AS4777
GB/
G83
IT/
DK5950
SP/
RD1663
dFac-Max
Hz/s
4
0,25
0.2
0.20
2
dZac-Max mOhm
685
20000
350
350
350
Fac-delta-
Hz
2,45
0,19
0.5
0.29
0.98
Fac-delta+
Hz
0,19
0,19
0.5
0.29
0.98
I-Ni-Test
mA
16000
8000
0
0
0
LDVtgC
V
0
50
50
50
50
T-Start
s
10
45
180
10
10
Uac-Min
V
198
205
209
198
199
Uac-Max
V
260
265
261
262
250