Schneider Electric 5000 Manual De Usuario

Descargar
Página de 19
 
 
15
 
 
   
P
ROBLEM AND 
P
OSSIBLE 
 
C
AUSE
 
S
OLUTION
 
BYPASS 
LED
 ILLUMINATES
 
The bypass switch has been 
turned on manually or through 
an accessory. 
If bypass is the chosen mode of operation, ignore the illuminated LED. 
If bypass is not the chosen mode of operation move the bypass switch on the 
back of the UPS, to the normal position. 
FAULT AND OVERLOAD 
LED
S ILLUMINATE
,
 
UPS
 EMITS A SUSTAINED ALARM TONE
 
The UPS has ceased sending 
power to connected equipment. 
The connected equipment exceeds the specified “maximum load” as defined in 
Specifications on the APC Web site, 
www.apc.com
.  
Disconnect nonessential equipment from the UPS to eliminate the overload 
condition. 
Press the OFF button, then the ON button to restore power to connected 
equipment. 
FAULT 
LED
 ILLUMINATES
 
Internal UPS fault. 
Do not attempt to use the UPS. Turn the UPS off and have it serviced 
immediately. 
REPLACE BATTERY 
LED
  ILLUMINATES
 
Replace Battery LED flashes and 
short beep is emitted every two 
seconds to indicate the battery is 
disconnected. 
Check that the battery connectors are fully engaged. 
Weak battery. 
Allow the battery to recharge for 24 hours. Then, perform a self-test. If the 
problem persists after recharging, replace the battery. 
Failure of a battery self-test. 
The UPS emits short beeps for one minute and the Replace Battery LED 
illuminates. The UPS repeats the alarm every five hours. Perform the self-test 
procedure after the battery has charged for 24 hours to confirm the Replace 
Battery
 condition. The alarm stops and the LED clears if the battery passes the 
self-test. 
UPS
 OPERATES ON BATTERY ALTHOUGH NORMAL LINE VOLTAGE EXISTS
 
Very high, low, or distorted line 
voltage. Inexpensive fuel 
powered generators can distort 
the voltage. 
Move the UPS to a different outlet on a different circuit. Test the input voltage 
with the utility voltage display. 
D
IAGNOSTIC 
U
TILITY 
V
OLTAGE
 
All five LEDs are illuminated 
The line voltage is extremely high and should be checked by an electrician. 
There is no LED illumination 
If the UPS is plugged into a properly functioning utility power outlet, the line 
voltage is extremely low. 
O
NLINE 
LED 
There is no LED illumination 
The UPS is running on battery, or it is not turned on. 
The LED is blinking 
The UPS is running an internal self-test.