6  Commissioning 
Issue 10/06 
 
MICROMASTER 440 
28 
Operating Instructions (Compact) 
6 Commissioning 
6.1 Quick 
commissioning 
The frequency inverter is adapted to the motor using the quick commissioning 
function and important technological parameters are set. The quick commissioning 
shouldn't be carried-out if the rated motor data saved in the frequency inverter 
(4-pole 1LA Siemens motor, star circuit configuration   frequency inverter (FU)-
specific) match the rating plate data. 
Parameters, designated with a * offer more setting possibilities than are actually 
listed here. Refer to the parameter list for additional setting possibilities. 
 
 
 
 Factory 
setting
 
P0003 = 3 
 
 
User access level * 
 1  Standard: Allows access into most frequently used parameters 
  2  Extended: Allows extended access e.g. to inverter I/O functions 
  3  Expert (For expert use only) 
 
Parameter filter
 
 0  All parameters 
 2  Inverter 
 3  Motor 
 4  Speed sensor
 
 
P0010 = 1 
 
 
Commissioning parameter * 
 0  Ready 
  1  Quick commissioning  
30 Factory 
setting 
NOTE 
P0010 should be set to 1 in order to parameterize the data of the motor rating 
plate. 
P0100 =...
 
 
Europe/ North America  
(enters the line supply frequency) 
 0  Europe [kW], frequency default 50 Hz 
  1  North America [hp], frequency default 60 Hz  
  2  North America [kW], frequency default 60 Hz 
NOTE 
For P0100 = 0 or 1, the setting of switch 
DIP50/60 
determines the value of 
P0100. 
    OFF  = 
kW, 50 Hz  
    ON  = 
hp, 60 Hz
 
 
Inverter application 
(enters the required torque) 
  0  Constant torque (e.g. compressors, processing machines) 
  1  Variable torque (e.g. pumps, fans) 
NOTE 
This parameter is only effective for drive inverters 
 5.5 kW / 400 V 
 
Select motor type 
  1  Asynchronous motor (induction motor) 
 2  Synchronous motor 
NOTE 
For P0300 = 2 (synchronous motor), only the V/f control types (P1300 < 20) are 
permitted. 
P010
0 =
 1, 2 
P010
0 =
 0 
START 
P0004 = 0 
 
P0300 =...  P0300 =...
 
P0205 =...  P0205 =...
1