6  Commissioning 
Issue 10/06 
 
MICROMASTER 440 
38 
Operating Instructions (Compact) 
ADC1
ADC2
OFF = [V], 0 - 10 V
ON   = [A], 0 - 20 mA
7
OFF = [V], 0 - 10 V
ON   = [A], 0 - 20 mA
6.4.6 
Analog input (ADC) 
 
 
 
ADC type 
Defines the analog input type and activates the monitoring 
function of the analog input. 
  0  Unipolar voltage input (0 to +10 V) 
  1  Unipolar voltage input with monitoring 
(0 to 10 V) 
  2  Unipolar current input (0 to 20 mA) 
  3  Unipolar current input with monitoring 
(0 to 20 mA) 
  4  Bipolar voltage input (-10 to +10 V)  
NOTE 
For P0756 to P0760, the following applies: 
Index 0  :  Analog input 1 (ADC1), terminals 3, 4 
Index 1  :  Analog input 2 (ADC2), terminals 10, 11 
 
P0757 =... 
 
Value x1 of ADC scaling 
 
 
P0758 =... 
 
Value y1 of ADC scaling 
This parameter represents the 
value of x1 as a % of P2000 
(reference frequency). 
 
P0759 =... 
 
Value x2 of ADC scaling 
 
 
P0760 =... 
 
Value y2 of ADC scaling 
This parameter represents the 
value of x2 as a % of P2000 
(reference frequency). 
 
Width of ADC deadband 
Defines width of deadband on 
analog input. 
ASPmax
100 %
10 V
20 mA
 V
 mA
x
100%
%
P0760
P0758
P0759
P0761 > 0
0 < P0758 < P0760  
||
  0 > P0758 > P0760
ASPmin
P0757
P0761
P0757 = P0761
4000 h
 
Delay, ADC signal loss 
Defines the delay time between the loss of the analog setpoint and fault message F0080 
being displayed. 
 
KL4
KL3
DIP switch
A
D
ADC
type
ADC
scaling
P
0757
P
0758
P
0759
P
0760
ADC
dead
zone
r0755
Pxxxx
r0752
P1000
ADC
ADC+
r0754
P0761
P0753
P0756
ADC
type
Setpoint
ADC channel
Wire
breakage
sensing
P0756
P0761
r0751
F0080
r0722
r0722.6
0
1
1.7 V
3.9 V
P0707
Pxxxx
Function
T
0
P0762
 
P0756 = ... 
0
P0762 = ... 
10 ms
 
0 V
 
0.0 %
 
10 V
 
100.0 %
0 V
 
 
P0761 =...