6  Commissioning 
MICROMASTER 440   
Operating Instructions (Compact) 
43
 
6.4.11 
Ramp function generator (RFG) 
 
Skip frequency 1 
(entered in Hz) 
Defines skip frequency 1, which avoids 
effects of mechanical resonance and 
suppresses frequencies within +/- p1101 
(skip frequency bandwidth). 
 
Skip frequency 2  
 
Skip frequency 3 
 
Skip frequency 4 
 
Skip frequency bandwidth
 
 
(entered in Hz) 
p1101
p1091
f
in
f
out
Skip frequency
bandwidth
Skip frequency
 
 
Ramp-up time
 
 
(enters the accelerating time in s) 
 
 
 
Ramp-down time
 
 
(enters the deceleration time in s) 
f
p1082
(f
max
)
f
1
t
p1120
p1121
 
Rump-up initial rounding time
  
(entered in s) 
 
Ramp-up final rounding time
 
 
(entered in s) 
 
Rump-down initial rounding time
  
(entered in s) 
 
Ramp-down final rounding time
 
 
(entered in s) 
 
Rounding type
 
 
 0  Continuous smoothing 
 1  Discontinuous smoothing 
P1133
P1132
P1131
P1130
t
f
f
2
f
1
t
up
t
down
 
The rounding times are recommended as 
abrupt responses can be avoided therefore 
reducing stress and damage to the mechanical 
system. 
The ramp-up and ramp-down times are 
extended by the component of the rounding 
ramps.
 
 
OFF3 ramp-down time
 
 
Defines ramp-down time from maximum frequency to standstill for OFF3 command. 
 
2.00 Hz
0.00 Hz
0.00 Hz
0.00 Hz
0.00 Hz
P1091 = ... 
P1092 = ... 
P1093 = ... 
P1094 = ... 
P1101 = ... 
P1120 = ... 
P1121 = ... 
P1130 = ... 
P1131 = ... 
P1132 = ... 
P1133 = ... 
P1134 = ... 
P1135 = ... 
10.00 s
10.00 s
0.00 s
 
0.00 s 
0.00 s 
5.00 s 
0.00 s