Battery Information
C–4
976-0043-01-02
Other options
Another option for 24 volt (only) alkaline battery banks is to use only 
19 cells instead of 20. Fewer cells allow the battery charger to operate 
more closely to the settings used for lead-acid batteries. However, the 
battery voltage will drop to as low as 18 volts when discharging the 
batteries.
Consult the battery manufacturer or supplier regarding system 
requirements and battery charger settings for alkaline type batteries.
Understanding Battery Capacity Ratings
Discharge rate
Deep cycle batteries have their amp-hour rating expressed as “at the x-
hour rate”. The hour rating refers to the time it takes to discharge the 
batteries. A faster hour rate (6 hour rate) means more current is 
withdrawn from the batteries during their discharge period. There is an 
inevitable amount of heat associated with the flow of current through a 
battery and the higher amount of current the greater the amount of heat 
will be generated. The heat is energy which is no longer available to the 
battery to power loads. a relatively long discharge rate (72 hour rate) will 
result in a larger number of amp-hours being available for electrical loads.
Calculation
This calculation shows how to determine the level of current drawn from 
a battery at any given hour rate—battery capacity divided by the hour rate 
equals the current drawn from the battery. For example, a battery rated 
220 Ah at a 6 hour rate would be discharged at 36 amps (220/6).
For most residential applications of the 
Sine Wave Plus
 the 72 hour rate is 
appropriate because on average a household uses low amounts of current 
(lights, TV, radio for example) with occasional bursts or higher 
consumption appliances like toasters or washing machines. For those 
installations where high continuous electrical consumption rates are 
anticipated it is more appropriate to use the 20 hour rate.
CCA rating
The CCA rating (cold cranking amps) shown on starting batteries 
expresses battery capacity in terms of its ability to provide large amounts 
of current for intervals measured in minutes, not hours. This is why 
starting batteries are not appropriate for inverter systems.
Battery Bank Sizing
Running time and 
size
The battery bank’s size determines the length of time the inverter can 
supply AC output power. The larger the bank, the longer the inverter can 
run.