Battery Configurations
976-0043-01-02
C–9
Battery Configurations
The battery bank must be wired to match the inverter’s DC input voltage 
specifications (24 or 48 Vdc). In addition, the batteries can be wired to 
provide additional run time. The various wiring configurations are: 
Series 
Wiring batteries in series increases the total bank output voltage. This 
voltage MUST match the DC requirements of the inverter or inverter and/
or battery damage may occur.
Parallel 
Wiring the batteries in parallel increases the total run time the batteries 
can operate the AC loads. The more batteries connected in parallel the 
longer the loads can be powered from the inverter.
Series-Parallel 
Series-parallel configurations increase both the battery voltage (to match 
the inverter’s DC requirements) and run-time for operating the AC loads. 
This voltage must match the DC requirements of the inverter.
Batteries with more than two or three series strings in parallel often 
exhibit poor performance characteristics and shortened life.
Wiring Batteries in Series
Effect
Wiring the batteries in a series configuration increases the voltage of the 
battery string. Six-volt batteries can be combined to form 24-volt or 48-
volt battery banks. In the same way, 12-volt batteries connected in series 
form 24-volt and 48-volt battery banks. The total current capacity of the 
bank does not increase and remains the same amp-hour rating as it does 
for a single battery.
Important
The voltage must match the DC requirements of the inverter.
Figure C-1 6-volt Battery Wiring - “Series” Configuration
+
-
+
-
6 V
6 V
+
-
24 V INVERTER
(Total battery capacity = 100 Ah)
+
-
+
6 V
6 V
-
+
-
+
-
6 V
6 V
+
-
48 V INVERTER
(Total battery capacity = 100 Ah)
+
-
+
-
6 V
6 V
+
-
+
-
6 V
6 V
+
-
+
-
6 V
6 V
Each battery’s amp-hour rating is 100 Ah.