Xantrex Technology SW Plus 4048 Manual De Usuario

Descargar
Página de 344
Battery Maintenance
976-0043-01-02
C–15
Equalization Charging
Purpose
An equalize charge helps to remove sulfate buildup on the battery plates 
and balances the charge of individual cells. 
Effect
Equalize charging also produces gassing which stirs up the electrolyte 
mixture and helps distribute the acid more evenly. 
Non-equalized 
batteries
Batteries that are not equalize charged can be damaged by sulfate 
accumulation, thus sealing off a percentage of the plates and reducing 
battery capacity. They may also have sulfuric acid accumulate at the 
bottom of the battery, potentially damaging the plates. At the same time, 
the electrolyte at the top of the battery gets watery. This effect is called 
stratification.
Frequency
Every month or two the batteries should be equalize charged.
Note:
If the battery temperature is allowed to fall to extremely cold 
temperatures, the inverter with a BTS may not be able to properly recharge cold 
batteries due to maximum voltage limits of the inverter. Ensure the batteries are 
protected from extreme temperatures.
CAUTION: Damage to DC Loads
The high voltages reached during an equalize charge may damage DC loads that 
are connected to the inverter. Disconnect any DC loads from the inverter before 
running an equalize charge.
CAUTION: Damage to Batteries
Equalization should be done for standard electrolyte vented batteries only. Sealed 
or GEL cell batteries should not be equalize charged. Consult your battery 
supplier for details on equalize charging for the battery type in your system.