Correcting Multi-wire Branch Circuit Wiring
976-0043-01-02
F–5
Correcting Multi-wire Branch Circuit Wiring
Acceptable options
Correcting multi-wire branch circuit wiring is not easy. Two options 
which will correct multi wiring branch circuit wiring are:
Rewire existing multi-wire branch circuits to conventional “home 
run” wiring. This requires a qualified electrician (knowledgeable 
about multi-wire branch circuit wiring) and is expensive. There may 
be multiple multi-wire branch circuits located throughout the 
structure, requiring complete rewiring.
Add a second inverter in a “series stacked” arrangement. This is an 
expensive solution, but would restore the original 240 Vac split-phase 
configuration. This solution may actually be less expensive than 
having an electrician re-wire the multi-wire branch circuits. It also 
provides increased power backup protection and can power 240 Vac 
loads.
Recommended 
option
Add a step-down autotransformer to the output of the inverter to restore 
the split-phase configuration. This is the least expensive and easiest 
method to correct for multi-wire branch circuit wiring. Refer to 
. Using this method, half of the current is supplied to one leg of the 
circuit and half to the other in a split-phase arrangement (180° out-of-
phase). This will restore the original functionality and safety to the multi-
wire branch circuit.
WARNING: Fire Hazard
Until one of the solutions above is implemented, a stand-alone 120 Vac inverter 
(or generator) must not be installed where multi-wire branch circuits exist.