Powerware UPS20-30kVA Manual De Usuario

Descargar
Página de 52
9
UPS 20-30 kVA, 230 V 0/60 Hz output  
User’s Guide
1026743 
Revision B
A parallel UPS system means the linking together of two or more UPS units in parallel so that in 
the unlikely event one fails the other can automatically take up the load. Traditionally a parallel 
redundancy configuration is achieved by having a random or fixed master-slave relationship 
among the UPS units. This master logic gives out individual commands to all the slaves units. 
Unfortunately this can lead to a single-point-of-failure for the whole system because if the master 
logic or communication to slaves fails, and causes the whole UPS system to be in trouble.
The Hot Sync® technology was developed to allow parallel capacity system and to maintain 
the highest system availability. An industry leading paralleling technology in its own right, 
the patented Hot Sync enables you to set up a parallel redundant system giving you 100% 
conditioned power at all times. Its unique digital design eliminates the system level single 
point of failure inherent in traditional parallel UPS modules, and exponentially increases the 
reliability of the overall system.
Hot Sync allows up to four UPS units to cover the same load in parallel and redundant 
configuration. No vulnerable master logic is needed in this patented design. It provides 
automatic load sharing and module level redundancy with nothing other than the power 
connecting the Hot Sync version of UPS modules.
Basic system configuration
The following basic UPS system configurations are available:
A single UPS system: 
- UPS cabinet with 0-4 battery strings 
20-30 kVA 
- Runtime with internal batteries   
20 kVA: up to 31 minutes 
 
 
 
 
 
 
30 kVA: up to 20 minutes 
 
 
 
- External battery cabinet   
 
For longer runtimes 
- LCD display for easy configuration 
Standard 
- Remote display   
 
 
Optional
A parallel UPS system 
- Up to four units can be paralled
Figure 2 UPS configuration with two External Battery Cabinets.
Adding optional accessories can enhance the UPS system configuration. These include for 
example XSlot communication adapters.