UNDERSTANDING UPS OPERATION
EATON Powerware
®
 9395 UPS (1000–1100 kVA) Installation and Operation Manual  
S
  164201764 Rev 1 www.powerware.com
6−8
Input Breaker
(CB1)
(optional)
E1, E2, E3
E6, E7,
E8, E12
NOTE  Callout letters 
A
B
C
, and 
D
NOTE  If the load requires a neutral, a bypass source neutral must be provided. If the load does not require a neutral and there is no neutral conductor
connected at the bypass input, a neutral to ground bonding jumper must be installed. DO NOT install both a source neutral and a bonding jumper.
UPS CABINET
Backfeed
Contactor (K5)
E9,
E10,
E11,
E12
Static
Switch
AC Input to
UPS Rectifier
3 Wire A−B−C
Rotation
AC Input to
Bypass
3 or 4 Wire A−B−C
Rotation
Fuse
Service Connector
Battery
Converter
Inverter
Output
Contactor
(K3)
Fuse
Rectifier
Input
Contactor
(K1)
Battery Contactor (K2)
Fuse
Fuse
Fuse
UPM 2
Battery
Breaker
E4. E5
Battery
Converter
Inverter
Output
Contactor
(K3)
Fuse
Rectifier
Input
Contactor
(K1)
Battery Contactor (K2)
Fuse
Fuse
Fuse
UPM 3
Battery
Breaker
E4. E5
Battery
Breaker
E4. E5
Battery
Converter
Inverter
Output
Contactor
(K3)
Fuse
Rectifier
Input
Contactor
(K1)
Battery Contactor (K2)
Fuse
Fuse
Fuse
UPM 1
Bypass
Breaker
(CB4)
Battery
Converter
Inverter
Output
Contactor
(K3)
Fuse
Rectifier
Input
Contactor
(K1)
Battery Contactor (K2)
Fuse
Fuse
Fuse
UPM 4
X−Slot 
Interface
48V Battery
Shunt Trip
Interface Board
Battery Aux
Remote EPO
Building Alarms
Alarm Relays
FI−UPM CABINET
Battery
Breaker
A
B
C
D
C
C
AC Output
to Critical
Load
C
BATTERY SYSTEM
(Not supplied with the UPS)
BATTERY SYSTEM
(Not supplied with the UPS)
BATTERY SYSTEM
(Not supplied with the UPS)
BATTERY SYSTEM
(Not supplied with the UPS)
Figure 6-6. Four UPM UPS System, Output Dual-Feed, Separate Battery System