Powerware 9315s Manual De Usuario

Descargar
Página de 205
A---45
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A
092402
Table P. UPM Output-to-SSBM Cable and Conduit Configurations: For Max Number of UPMs
UPM Output-to-SSBM Cable Configuration
Minimum Conductor Size, 3, (1) Neutral, (1) Gnd
Max No. of UPMs Connectable to each SSBM
(Based on UPM-to-SSBM Cable Configuration
9315
Model - kVA/kW
Output
Voltage
Output
Current
Conductor Size
(AWG or kcmil)
Number of
Conductors per
∅ and Neutral
Number and
Size of Conduit
(in inches)
Model 2500
Model 3000
Model 4000
200 --- 200/160
400
290
500
1
1 --- 3.5
8
8
8
225 --- 225/180
208
625
500
2
2 --- 3.5
7
7
7
225 --- 225/180
480
271
400
1
1 --- 3.0
8
8
8
300 --- 225/180
480
271
400
1
1 --- 3.0
8
8
8
300 --- 225/180
600
217
300
1
1 --- 3.0
8
8
8
300 --- 300/240
208
830
400*
3
3 --- 3.0
4
4
4
300--- 300/240
480
360
4/0
2
2 --- 2.5
7
7
7
300--- 300/240
600
289
500
1
1 --- 3.5
8
8
8
250 --- 200/160
400
290
500
1
1 --- 3.5
8
8
8
250 --- 250/200
400
360
4/0
2
2 --- 2.5
7
7
7
400 --- 300/240
400
433
300
2
2 --- 3.0
7
7
7
400 --- 400/320
400
577
500
2
2 --- 3.5
7
7
7
500 --- 400/320
208
1110
500*
4
4 --- 3.5
3
3
3
500 --- 400/320
480
480
350
2
2 --- 3.0
7
7
7
500 --- 500/400
480
600
500
2
2 --- 3.5
7
7
7
500 --- 500/400
600
480
350
2
2 --- 3.0
7
7
7
625
500/400
400
722
350
3
3 --- 3.0
4
4
4
625 --- 500/400
400
722
700
2
2 --- 4.0
7
7
7
625
500/450
400
722
350
3
3 --- 3.0
4
4
4
625 --- 500/450
400
722
700
2
2 --- 4.0
7
7
7
625 --- 625/500
400
902
500
3
3 --- 3.5
4
4
4
625 --- 626/562
400
902
500
3
3 --- 3.5
4
4
4
750
625/500
480
752
350
3
3 --- 3.0
4
4
4
750 --- 625/500
480
752
700
2
2 --- 4.0
7
7
7
750 --- 625/500
600
601
500
2
2 --- 3.5
7
7
7
750
625/562
480
752
350
3
3 --- 3.0
4
4
4
750 --- 625/562
480
752
700
2
2 --- 4.0
7
7
7
750 --- 625/562
600
601
500
2
2 --- 3.5
7
7
7
750 --- 750/600
480
902
500
3
3 --- 3.5
4
4
4
750
750/600
600
722
350
3
3 --- 3.0
4
4
4
750 --- 750/600
600
722
700
2
2 --- 4.0
7
7
7
750 --- 750/675
480
902
500
3
3 --- 3.5
4
4
4
750
750/675
600
722
350
3
3 --- 3.0
4
4
4
750 --- 750/675
600
722
700
2
2 --- 4.0
7
7
7
DESCRIPTION:
DRAWING NO:
SHEET:
164201373---14
UPM OUTPUT-TO-SSBM CABLE AND
2 of 2
CONDUIT CONFIGURATIONS
NOTES:
1. The cable configurations shown support connection of the maximum number of UPMs for each SSBM model. The maximum number
of UPMs connected to any SSBM shall not exceed eight.
2. Maximum conductor size considered: 700 kcmil.
3. * = Connections to output transformer, not UPM. Refer to applicable Powerware 9315 UPS Installation manual for UPS cable requirements
between the UPS and its output transformer.