Toshiba VF-AS1 Manual De Instrucciónes

Descargar
Página de 73
E6581315
23
4.5. 
 
Examples of the use of communication commands
Here are some examples of the use of communication commands provided for the VF-AS1 series of
inverters.
Inverter numbers and checksum used in ASCII mode are omitted from these examples.
„
  Examples of communication
- To run the motor in forward direction with the frequency set to 60 Hz from the computer
<ASCII mode>
Computer 
→ Inverter
Inverter 
→ Computer
(PFA011770)
CR
(PFA011770)
CR
…Set the operation frequency to 60 Hz.
(60 / 0.01 Hz = 6000 = 1770H)
(PFA00C400)
CR
(PFA00C400)
CR
…Set to “forward run” with commands and frequency
instruction from the computer enabled.
<Binary mode>
Computer 
→ Inverter
Inverter 
→ Computer
2F 50 FA 01 17 70 01
2F 50 FA 01 17 70 01
2F 50 FA 00 C4 00 3D
2F 50 FA 00 C4 00 3D
- To monitor the output frequency (during 60 Hz operation)
<ASCII mode>
Computer 
→ Inverter
Inverter 
→ Computer
(RFD00)
CR
(RFD001770)
CR
…Set the operation frequency to 60 Hz.
(60
÷0.01Hz=6000=1770H)
<Binary mode>
Computer 
→ Inverter
Inverter 
→ Computer
2F 52 FD 00 7E
2F 52 FD 00 17 70 05
- To monitor the status of the inverter
<ASCII mode>
Computer 
→ Inverter
Inverter 
→ Computer
(RFD01)
CR
(rFD010003)
CR
 
…For details on statuses, see 8.2 “Monitoring from
the computer.” (Stop status, FL output status, trip
status (r command))
<Binary mode>
Computer 
→ Inverter
Inverter 
→ Computer
2F 52 FD 01 7F
2F 72 FD 01 00 03 A2
- To check the trip code (when the inverter is tripped because of )
…For details on trip codes, see “Trip code monitor” in 8.2, “Monitoring
from the computer.” (18H = 24d “” trip status)
<ASCII mode>
Computer 
→ Inverter
Inverter 
→ Computer
(RFC90)CR
(rFC900018)CR
<Binary mode>
Computer 
→ Inverter
Inverter 
→ Computer
2F 52 FC 90 0D
2F 72 FC 90 00 18 45