Mitsubishi Electronics 700 Series Manual De Usuario

Descargar
Página de 183
49
CC-Link Parameters
2
2.2 CC-Link Parameters
2.2.1
CC-Link Extended Setting (Pr. 544)
Remote register function can be extended.
*1
The program used for conventional series inverter (FR-A5NC) can be used.
*2
When using double, quadruple and octuple settings of the CC-Link Ver.2, station data of
the master station must be set to double, quadruple and octuple also.
(If the master station is CC-Link Ver.1 compatible station, the above setting can not be
made.) 
Parameter 
Number
Name
Initial 
Value
Setting 
Range
Description
CC-Link 
Ver.
544
CC-Link extended 
setting
0
0
1
Occupies one station
(FR-A5NC compatible) 
1
Occupies one station
12 
2
Occupies one station double
14 
Occupies one station 
quadrople
18 
Occupies one station octuple
100
1
Occupies one station
(PLC function)
112 
2
Occupies one station double 
(PLC function)
114 
Occupies one station 
quadrople (PLC function)
118 
Occupies one station octuple 
(PLC function)
REMARKS
The setting change is reflected after an inverter reset.