Toshiba 125 Manual De Usuario

Descargar
Página de 120
51
G8000 Series Installation and Operation Manual
G8000 Specifications
Model Number
T80S3K08
KK6XSxx
T80S3K10
KK6XSxx
T80S3K12
KK6XSxx
T80S3K15 
KK6Xxx
T80S3K22 
KK6XSxx
T80S3K30 
KK6XSxx
T80S3K50 
KK6XSxx
Environ-
ment 
(cont.)
Dimension - Width
36.8 in. (935 mm)
55.1 in. (1400 mm)
76.8 in.  
1951 mm)
101.8 in.
(2586 mm)
Depth
32.5 in. (826 mm)
31.8 in. (808 mm)
35.7 in. 
(907 mm)
37.4 in.
(945 mm)
Height
79.2 in. (2012 mm)
79.4  in.  
(2017 mm)
79.7 in.
(2024 mm)
Cable Access
Bottom Access
Top or Bottom Access
Top Access
Minimum 
Clearance
Top:    15.75” (400 mm)
Front:  43 7/16” (1100 mm)
37 in. 
(940 mm)
Back/Left/Right Sides: Zero
Enclosure
NEMA 1
Heat Loss to be 
Removed @ Full 
Load
28,321  
BTUs/hr
 33,746  
BTUs/hr
37,281  
BTUs/hr
38,524  
BTUs/hr
67,667   
BTUs/hr
89,011   
BTUs/hr
110,262  
BTUs/hr
Audible Noise
65 dBA @ 1m Typical
68 dBA @ 1m Typical
72 dBA @ 
1m Typical
78 dBA @ 
1m Typical
Operating Tem-
perature
32˚F to 86˚F (0˚C to 30˚C) for 1.0PF   32˚F to 104˚F (0˚C to 40˚C) for 0.8 PF
Operating Humid-
ity 
30% to 90% Non-Condensing
Operating Altitude
3200 ft. (1000 m)
Listings/Standards UL 1778; UL 17025, cUL 22.2, No. 107.1; ANSI C62.41 (IEEE 587 Cat B) NFPA 70; OSHA; ISO 
9001; IEC298 IP20
Monitor-
ing
Warranty
3 Years Parts and Labor
Dry Contacts 
Included
Yes, for input and output signals
RS232 Port
Included
Intelligent Monitor-
ing (Optional)
SNMP; Modbus RTU; Modbus TCP; BACNET, METASYS
Display
LCD Touch Panel for Local Monitoring, Operation and control
EPO
 Emergency Power 
Off
Included
Config-
uration
Input Conv.
6-diode Bridge  Rectifier
Battery  Cct
IGBT Chopper
Out. Inv.
IGBT Converter with PWM