6.19.6  Output Voltage Adjustment 
 
When the MENU key is pressed and held 3-4 seconds during normal 'AC Input Mode' of 
 
operation, the LCD screen displays the output voltage on the present output voltage adjust 
 screen: 
 
  OUTPUT VOLT.  ADJUST 
OUTPUT VOLTAGE.=###% 
>F1:DATA  SET  MODE 
Δ/∇ :PREV/NEXT  SCREEN 
 
 
 
Press the F1 key to display the following active adjustment screen: 
 
 
    OUTPUT VOLT. ADJUST 
REFERENCE ADJUST: ## 
Δ/∇ :CHANGE  DATA 
>ENTER: ACCEPT  CHANGE 
 
 
 
The locations marked ## will show the numerical value of the allowable voltage adjustment 
 
parameter values. Press the 'up' and 'down' arrow keys to adjust the setting from between 
 
±5 volts. This will cause the unit's output voltage to adjust to within ±2% of its nominal 
 value. 
 
 
If the inverter is not running, and the output voltage cannot be adjusted; the following 
 
message will be displayed: 
 
OUTPUT VOLT. ADJUST 
ADJUST PROHIBITED 
DATA CANNOT CHANGE 
>
Δ/∇:PRV/NEXT SCREEN 
 
 
 
Pressing the F1 key will have no effect on this display screen 
 
 
6.19.7  Equalize Charge Mode Select 
 
Contact Toshiba Customer Support toll free at 1-877-867-8773 before using this option.   
 
 
DAMAGE to the battery system may occur if this option is used improperly. 
 
4200FA CT/XT User’s Manual 
 
 
56