DMC-1400  Series Command Reference _LR* 
● 131   
_LR* 
FUNCTION:  Reverse Limit Switch Operand (Keyword) 
DESCRIPTION: 
*The _LR operand contains the state of the reverse limit switch. 
Note:  This is not a command. 
NOTE:  This operand is affected by the configuration of the limit switches set by the 
command CN: 
 
For CN-1: 
 
 
_LRx = 1 when the limit switch input is inactive* 
 
 
_LRx = 0 when the limit switch input is active* 
 
For CN 1: 
 
 
_LRx = 0 when the limit switch input is inactive* 
 
 
_LRx = 1 when the limit switch input is active* 
* The term “active” refers to the condition when at least 1 ma of current is flowing through 
the input circuitry.  The input circuitry can be configured to sink or source current to 
become active.  See Chapter 3 of product manual for further details. 
EXAMPLES: 
MG _LR  
Display the status of the reverse limit switch 
JP#A,_LR=0 
Jump to label, #A, when reverse limit switch is activated 
*This is an Operand – Not a command.