3.2.4.7.  fd01 (Inverter operating status 1) 
 
bit Function 
Note 
Failure FL 
No output 
Under in 
progress 
1 Failure 
Not 
tripped 
Tripped 
Trip status includes rtry and 
the trip retention status are also 
regarded as tripped statuses. 
Alarm 
No alarm 
Alarm issued 
Under voltage (moff) Normal  Under 
voltage 
Motor selection (1 or 2) 
(THR 2 selection) 
Motor 1 (THR1)
Motor 2 (THR2)
THR1:  pt = setting value, vl, 
vlv
, vb, thr 
THR2: pt = 0, f170, f171, 
f172
, f173 
PID control off 
PID control   
permitted 
PID control   
prohibits 
Acceleration/deceleratio
n pattern selection (1 or 
2) 
Acceleration/dec
eleration pattern 
1 (AD1) 
Acceleration/dec
eleration pattern 
2 (AD2) 
AD1: acc, dec 
AD2: f500, f501 
7 DC 
braking 
OFF 
Forced DC 
braking 
Jog run 
OFF 
Jog run 
Forward / reverse run 
Forward run 
Reverse run 
10 Run/stop 
Stop 
Run 
11 
Coast stop (ST = OFF) 
ST=ON 
ST=OFF 
12 Emergency 
stop 
No emergency   
stop status 
Emergency  
stop status 
13 
Standby ST=ON 
Start-up process
Standby 
Standby: Initialization 
completed, not failure stop 
status, not alarm stop status 
(moff, ll forced stop), 
ST=ON, and RUN=ON 
14 Standby 
Start-up 
process
Standby 
Standby: Initialization completed, 
not failure stop status and not 
alarm stop status (moff, ll 
forced stop) 
15 (Reserved) 
Undefined 
Note: Don’t use the reserved bit for the judgment. 
 
3.2.4.8.  fd00 (Output frequency) 
 
The current output frequency is read into 0.01Hz of units and by the hexadecimal number.   
For example, when the output frequency is 80Hz, 0x1F40 (hexadecimal number) are read. 
 
Since the minimum unit is 0.01%, 
0x1F40 (Hex.)    = 8000(Dec.) * 0.01 = 80 (Hz) 
 
Also about the following parameters, these are the same as this. 
- fd22 (Feedback value of PID)............................................... Unit: 0.01Hz 
- fd16 (Estimated speed) ........................................................ Unit: 0.01Hz 
- fd29 (Input power) ................................................................ Unit: 0.01kW 
- fd30 (Output power) ............................................................. Unit: 0.01kW