Cisco Systems N7KF248XT25EP1 Manual De Usuario

Descargar
Página de 204
S e n d   d o c u m e n t   c o m m e n t s   t o   n e x u s 7 k - d o c f e e d b a c k @ c i s c o . c o m
A-12
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
OL-18634-01
Appendix A      Technical Specifications
Facility Cooling Requirements
Facility Cooling Requirements
The Cisco Nexus 7000 Series switches dissipate considerable power that generates much heat. The 
following is the heat dissipation requirement for these switches:
  •
Cisco Nexus 7010 dissipates up to 35,162 BTUs per hour
  •
Cisco Nexus 7018 dissipates up to 51,195 BTUs per hour
Chassis Airflow
The Cisco Nexus 7000 Series switches use either front-to-back or side-to-side airflow for device cooling. 
The Cisco Nexus 7010 switch uses front-to-back airflow as shown in 
, and the Cisco Nexus 
7018 switch uses side-to-side airflow to cool its modules and front-to-back airflow to cool its power 
supply units as shown in 
. Both switches are designed to work in a hot-aisle/cold-aisle 
environment, but the Cisco Nexus 7018 switch design also requires side clearances to allow airflow in 
and out the sides. 
Figure A-13
Airflow for the Cisco Nexus 7010 Chassis
270544
2
3