S e n d   d o c u m e n t a t i o n   c o m m e n t s   t o   n e x u s 5 k d o c s @ c i s c o . c o m .
A-1
Cisco Nexus 6000 Series Hardware Installation Guide
OL-15902-02
A P P E N D I X
A
Cabinet and Rack Installation
This appendix provides the requirements for cabinet and rack installation for the Cisco Nexus 6004 
switch and includes the following sections:
Cabinet and Rack Requirements
This section provides the requirements for the following types of cabinets and racks, assuming an 
external ambient air temperature range of 0 to 104
o
F (0 to 40
o
C):
Standard perforated cabinets
Standard open racks
Note
If you are selecting an enclosed cabinet, we recommend one of the thermally validated types: standard 
perforated or solid-walled with a fan tray.
Note
Do not use racks that have obstructions (such as power strips), because the obstructions could impair 
access to field-replaceable units (FRUs).
This section includes the following topics:
General Requirements for Cabinets and Racks
The cabinet or rack must be one of the following types:
Standard 19-in. (48.3 cm) (four-post EIA cabinet or rack, with mounting rails that conform to 
English universal hole spacing per section 1 of ANSI/EIA-310-D-1992. See the 
.
The cabinet or rack must also meet the following requirements:
The minimum vertical rack space for the Cisco Nexus 6004 chassis must be four RU (rack units).