Appendix A      Cabinet and Rack Installation
    Cable Management Guidelines
The width between the rack-mounting rails must be at least 19 inches if the rear of the switch is not 
attached to the rack. For four-post EIA racks, this is the distance between the two front rails.
For four-post EIA cabinets (perforated or solid-walled), the requirements are as follows: 
The minimum spacing for the bend radius for fiber-optic cables should have the front-mounting 
rails of the cabinet offset from the front door by a minimum of 3 inches (7.6 cm), and a 
minimum of 5 inches (12.7 cm) if cable management brackets are installed on the front of the 
chassis.
The distance between the outside face of the front mounting rail and the outside face of the back 
mounting rail should be 23.5 to 34.0 inches (59.7 to 86.4 cm) to allow for rear-bracket 
installation.
A minimum of 2.5 inches (6.4 cm) of clear space should exist between the side edge of the 
chassis and the side wall of the cabinet. No sizeable flow obstructions should be immediately 
in the way of chassis air intake or exhaust vents.
Note
Optional jumper power cords are available for use in a cabinet. See the 
Requirements Specific to Perforated Cabinets
A perforated cabinet is as a cabinet with perforated front and rear doors and solid side walls. In addition 
to the requirements listed in the 
perforated cabinets must meet the following requirements:
The front and rear doors must have at least a 60 percent open area perforation pattern, with at least 
15 square inches (96.8 square cm) of open area per rack unit of door height.
The roof should be perforated with at least a 20 percent open area. 
The cabinet floor should be open or perforated to enhance cooling
.
Cisco provides an R-Series rack that conforms to these requirements. 
Cable Management Guidelines
To help with cable management, you might want to allow additional space in the rack above and below 
the chassis to make it easier to route as many as 56 fiber or copper cables through the rack.