Cisco Systems N6KC600164P Manual De Usuario

Descargar
Página de 204
S e n d   d o c u m e n t   c o m m e n t s   t o   n e x u s 7 k - d o c f e e d b a c k @ c i s c o . c o m
6-10
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
OL-18634-01
Chapter 6      Managing the Device Hardware
Power Supply Configuration Modes
SUMMARY STEPS
1.
config t
2.
power redundancy-mode mode
DETAILED STEPS
To configure the power supply mode, follow these steps:
Table 6-2
Power Availability for 7.5-kW Power Supply Units  
Combined
 
Mode
Power 
 
Supply
 
Redundancy
 
Mode
Input Source
 
Redundancy
 
Mode
Full
 
Redundancy
 
Mode
Dual inputs per power supply unit
220-V and 220-V inputs
1 power supply unit
7500 W
3750 W
2 power supply units
15,000 W
7500 W
7500 W
7500 W
3 power supply units
22,500 W
15,000 W
11,250 W
11,250 W
4 power supply units
30,000 W
22,500 W
15,000 W
15,000 W
Single input per power supply unit
220-V input
1 power supply unit
3750 W
2 power supply units
7500 W
3750 W
3 power supply units
11,250 W
7500 W
4 power supply units
15,000 W
11,250 W
Command 
Purpose
Step 1
config t
Example:
switch# config t
switch(config)# 
Enters configuration mode.
Step 2
power redundancy-mode 
combined|ps-redundant|insrc-redundant|
 
redundant
Example:
switch(config)# power redundancy-mode 
redundant
 
switch(config)# 
Configures one of the following power supply modes:
  •
For combined mode, use the combined keyword.
  •
For power supply redundancy, use the 
ps-redundant keyword.
  •
For input source redundancy, use the 
insrc-redundant keyword.
  •
For full redundancy, use the redundant keyword.